Gamewell-FCI Recalls to Upgrade Software Used with Fire Alarm System Control Boards
Gamewell-FCI Recalls to Upgrade Software Used with Fire Alarm System Control Boards
Recalling Firm: Gamewell-FCI, of Northford, Conn.
Reason for Recall / Hazard
Incoming and outgoing messages to and from the control board can interfere with each other, preventing it from sending a message to the command center in the event of fire.
Product Description & Identification
The software upgrade involves Gamewell-FCI model ILI-MB-E3 and ILI-S-E3 loop control boards. These boards are components of the Gamewell-FCI E3 Series fire alarm system. They provide the signaling line circuits and display information for the system.
Affected Products
Gamewell-FCI Electronic Control Boards by Honeywell
Additional Source Details
| Field | Value |
|---|---|
| U R L | https://www.cpsc.gov/Recalls/2007/Gamewell-FCI-Recalls-to-Upgrade-Software-Used-with-Fire-Alarm-System-Control-Boards |
| Title | Gamewell-FCI Recalls to Upgrade Software Used with Fire Alarm System Control Boards |
| Images › U R L | https://www.cpsc.gov/~/link/da178bd111c44efd8a5f0be3687d2d1e.jpg |
| Images › Caption | Control Board Using Recalled Software |
| Hazards › Name | Incoming and outgoing messages to and from the control board can interfere with each other, preventing it from sending a message to the command center in the event of fire. |
| Injuries › Name | Gamewell-FCI has received one report of failed communications during an electrical short that was not due to a fire. There have been no reports of property damage or injury. |
| Products › Name | Gamewell-FCI Electronic Control Boards by Honeywell |
| Products › Type | Home Control/Alarm Systems |
| Products › Category I D | 1999 |
| Products › Number Of Units | About 700 |
| Recall I D | 3799 |
| Remedies › Name | Gamewell-FCI is contacting customers directly and is providing a free firmware software upgrade. |
| Retailers › Name | Authorized distributors nationwide from October 2005 through September 2006. Authorized distributors resell and install loop control boards for commercial end users in facilities such as hotels and office buildings. |
| Recall Date | 2007-01-31T00:00:00 |
| Description | The software upgrade involves Gamewell-FCI model ILI-MB-E3 and ILI-S-E3 loop control boards. These boards are components of the Gamewell-FCI E3 Series fire alarm system. They provide the signaling line circuits and display information for the system. |
| Recall Number | 07526 |
| Manufacturers › Name | Gamewell-FCI, of Northford, Conn. |
| Consumer Contact | For more information, contact Gamewell-FCI at (800) 633-1311 between 8 a.m. and 5 p.m. ET Monday through Friday, or visit their distributor's Web site at www.gamewell-fci.com |
| Last Publish Date | 2014-05-23T00:00:00 |
| Manufacturer Countries › Country | United States |
Check Other Products In Your Household
Free Safety ToolsSafety recalls are issued daily across foods, medications, vehicles, and electronics. Use our instant tools to check your home for active safety warnings:
Overview
- Recalling FirmGamewell-FCI, of Northford, Conn.
📢 Share Warning
Alert family and friends to keep them safe. Copy this quick alert message:
🚨 SAFETY ALERT: Gamewell-FCI, of Northford, Conn. - Gamewell-FCI Recalls to Upgrade Software Used with Fire Alarm System Control Boards Check if your household is affected: https://therecallfile.com/recalls/gamewell-fci-recalls-to-upgrade-software-used-with-fire-alarm-system-c/CPSC-07526
Join Alertlist
Get instant email updates whenever critical safety recalls like this are published.
Support The Recall File
Help keep official recall alerts free, accessible, and fast for everyone.