Home/Recalls/CPSC-16134
CPSCGeneral Alert

Gamewell-FCI Recalls Fire Alarm Panels Due to Failure to Alert of a Fire, Smoke ...

Published: March 31, 2016Recall ID: 16134Category: generalCountry: US

Reason for Recall / Hazard

When configured in a certain way, the panels can become non-responsive and connected detectors in the area can fail to detect and respond to an alarm.

Product Description & Identification

This recall is for the ILI-MB-E3 and ILI-S-E3 Gamewell-FCI fire alarm panels in commercial buildings. This issue is limited to a specific configuration of Signaling Line Circuit (SLC) devices. To occur, the SLC must include at least two of the following detectors in any combination: Acclimate, 4-Warn, Photo/CO and iFAAST. The issue would occur only if the detectors are addressed within the same FlashScan polling group. Detectors installed in a different combination are not affected.

Affected Products

Gamewell-FCI fire alarm panels (ILI-MB-E3 and ILI-S-E3)

Additional Source Details

FieldValue
U R Lhttps://www.cpsc.gov/Recalls/2016/Gamewell-FCI-Recalls-Fire-Alarm-Panels
TitleGamewell-FCI Recalls Fire Alarm Panels Due to Failure to Alert of a Fire, Smoke or CO
Images › 1 › U R Lhttps://www.cpsc.gov/s3fs-public/Fire-Alarm-Panel.jpg
Images › 1 › CaptionFire Alarm Panel
Images › 2 › U R Lhttps://www.cpsc.gov/s3fs-public/ILI-MB-E3-Kinetis-Panel.jpg
Images › 2 › CaptionILI-MB-E3-KINETIS Panel
Images › 3 › U R Lhttps://www.cpsc.gov/s3fs-public/IL-S-E3-Kinetis-Panel.jpg
Images › 3 › CaptionILI-S-E3-KINETIS Panel
Hazards › NameWhen configured in a certain way, the panels can become non-responsive and connected detectors in the area can fail to detect and respond to an alarm.
Injuries › NameNo incidents or injuries have been reported.
Products › NameGamewell-FCI fire alarm panels (ILI-MB-E3 and ILI-S-E3)
Products › TypeFire or Smoke Alarms
Products › Category I D67943
Products › Number Of UnitsAbout 1,000
Recall I D6692
Remedies › NameConsumers should immediately contact the distributor to obtain the free repair, a firmware upgrade.
Retailers › NameAuthorized distributors from May 2015 through August 2015 for about $800.
Recall Date2016-03-31T00:00:00
DescriptionThis recall is for the ILI-MB-E3 and ILI-S-E3 Gamewell-FCI fire alarm panels in commercial buildings. This issue is limited to a specific configuration of Signaling Line Circuit (SLC) devices. To occur, the SLC must include at least two of the following detectors in any combination: Acclimate, 4-Warn, Photo/CO and iFAAST. The issue would occur only if the detectors are addressed within the same FlashScan polling group. Detectors installed in a different combination are not affected.
Distributors › NameGamewell-FCI of Northford, Conn.
Recall Number16134
Remedy Options › OptionRepair
Consumer ContactGamewell-FCI at 800-274-4324 from 7 a.m. to 7 p.m. ET Monday through Friday or online at www.gamewell-fci.com and click on "Safety Recall" for more information.
Last Publish Date2016-03-31T00:00:00
Manufacturer Countries › CountryUnited States