Reason for Recall / Hazard

These sprinklers are defective and are likely to fail to operate in a fire, thereby exposing consumers to the risk of death or serious injury.

Product Description & Identification

SCM's Star ME-1 sprinklers have the following information molded onto the sprinkler: the name "Star," the designation "ME-1," and the year of manufacture starting with 1983 and ending with 1995. These sprinklers were typically installed in areas of buildings where the sprinklers or water supply pipes may be subject to freezing. Examples of such areas include unheated attics, freezers and coolers, porches and parking garages. The types of facilities in which the sprinklers were installed include nursing homes, convalescent and long-term care facilities, supermarkets and other stores, warehouses, hospitals, and office buildings.

Affected Products

Star ME-1 dry fire sprinklers

Additional Source Details

FieldValue
U R Lhttps://www.cpsc.gov/Recalls/2003/CPSC-Warns-Consumers-to-Replace-Star-ME-1-Dry-Fire-Sprinklers-Made-by-Sprinkler-Corporation-of-Milwaukee----Administrative-Lawsuit-Settled-Firm-Financially-Unable-to-Conduct-Recall-----
TitleCPSC Warns Consumers to Replace Star ME-1 Dry Fire Sprinklers Made by Sprinkler Corporation of Milwaukee -- Administrative Lawsuit Settled, Firm Financially Unable to Conduct Recall --
Images › 1 › U R Lhttps://www.cpsc.gov/s3fs-public/Star-ME-1-sprinkler_0.jpg
Images › 1 › CaptionRecalled Star ME-1 dry fire sprinkler
Images › 2 › U R Lhttps://www.cpsc.gov/s3fs-public/Star-ME-1-sprinkler-2_0.jpg
Images › 2 › CaptionRecalled Star ME-1 dry fire sprinkler
Hazards › NameThese sprinklers are defective and are likely to fail to operate in a fire, thereby exposing consumers to the risk of death or serious injury.
Injuries › NameCPSC has received reports of two failures involving Star ME-1 dry sprinklers. One report involved a 1976 sprinkler, and the other, sprinklers installed in 1990.
Products › NameStar ME-1 dry fire sprinklers
Products › TypeSprinklers (Fire)
Products › Category I D2148
Products › Number Of UnitsApproximately 400,000
Recall I D2386
Remedies › NameBecause SCM is no longer in operation and has no assets, it is unable to conduct a recall, so no free replacement or refund is available for its sprinklers. Nevertheless, SCM urges building owners to follow CPSC guidance by inspecting the sprinkler systems in their buildings and replacing any Star ME-1 fire sprinklers manufactured from 1983 through 1995.
Retailers › NameThese sprinklers were typically installed in areas of buildings where the sprinklers or water supply pipes may be subject to freezing. Examples of such areas include unheated attics, freezers and coolers, porches and parking garages. The types of facilities in which the sprinklers were installed include nursing homes, convalescent and long-term care facilities, supermarkets and other stores, warehouses, hospitals, and office buildings.
Recall Date2003-04-25T00:00:00
DescriptionSCM's Star ME-1 sprinklers have the following information molded onto the sprinkler: the name "Star," the designation "ME-1," and the year of manufacture starting with 1983 and ending with 1995. These sprinklers were typically installed in areas of buildings where the sprinklers or water supply pipes may be subject to freezing. Examples of such areas include unheated attics, freezers and coolers, porches and parking garages. The types of facilities in which the sprinklers were installed include nursing homes, convalescent and long-term care facilities, supermarkets and other stores, warehouses, hospitals, and office buildings.
Recall Number03117
Manufacturers › NameSprinkler Corporation of Milwaukee, Inc. (SCM), formerly known as Star Sprinkler Corporation
Consumer ContactFor more information about testing and replacing dry type fire sprinklers, visit NFPA's website at www.nfpa.org. For more information on the SCM Star ME-1 fire sprinklers, call CPSC's Hotline at (800) 638- 2772 or visit the National Fire Sprinkler Association's website at www.nfsa.org