Home/Recalls/CPSC-02556
CPSCGeneral Alert

CPSC, Square D Company Announce Recall of Circuit Breakers

Published: August 9, 2002Recall ID: 02556Category: generalCountry: US

Reason for Recall / Hazard

The circuit breakers may have an incorrect torque load applied to the lug mounting screws. This could cause the clamping load between the lug and the circuit breaker terminals to be lower than specified, resulting in a high temperature condition. Products could overheat causing a fire hazard.

Product Description & Identification

This recall involves MA/MH circuit breakers manufactured between October 2000 and March 2002.

Affected Products

MA/MH circuit breakers

Additional Source Details

FieldValue
U R Lhttps://www.cpsc.gov/Recalls/2002/CPSC-Square-D-Company-Announce-Recall-of-Circuit-Breakers
TitleCPSC, Square D Company Announce Recall of Circuit Breakers
Images › U R Lhttps://www.cpsc.gov/s3fs-public/circuit-breaker.jpg
Images › CaptionRecalled MA/MH circuit breaker
Hazards › NameThe circuit breakers may have an incorrect torque load applied to the lug mounting screws. This could cause the clamping load between the lug and the circuit breaker terminals to be lower than specified, resulting in a high temperature condition. Products could overheat causing a fire hazard.
Injuries › NameNone reported.
Products › NameMA/MH circuit breakers
Products › TypeCircuit Breakers
Products › Category I D1881
Products › Number Of UnitsAbout 40,000
Recall I D2278
Remedies › NameContact Square D for a free repair. Repairs will consist of verifying proper screw torque and tightening all screws that do not meet the required torque specifications.
Retailers › NameThe circuit breakers were sold between October 2000 and March 2002 for between $3,000 and $9,000.
Recall Date2002-08-09T00:00:00
DescriptionThis recall involves MA/MH circuit breakers manufactured between October 2000 and March 2002.
Recall Number02556
Manufacturers › NameSquare D Company, of Palatine, Ill.
Consumer ContactFor more information, call (800) 634-8730 between 8 a.m. and 4 p.m. PT Monday through Friday.
Last Publish Date2025-11-14T00:00:00
Manufacturer Countries › CountryUnited States

Overview

  • Recalling FirmSquare D Company, of Palatine, Ill.
Official Agency Alert