Home/Recalls/CPSC-05589
CPSCGeneral Alert

CPSC, Kidde Announce Recall of Industrial Fire Extinguishers

Published: July 26, 2005Recall ID: 05589Category: generalCountry: US

Reason for Recall / Hazard

The nylon valves on these extinguishers can separate from the steel cylinder during the 6-year recharge service or shortly afterwards, creating a safety hazard to fire extinguisher service personnel and consumers.

Product Description & Identification

This Alert involves all Kidde 10 lb. dry chemical fire extinguishers manufactured with a black plastic Zytel® nylon valve assembly and a steel cylinder, between 1991 and 2000. These units were the subject of Kidde Service Bulletin 007 issued on July 21, 2004. These units were designed for commercial and industrial applications, and the majority of these units were placed into service in factories, plants, businesses and other commercial locations, as they require service by a qualified Fire Extinguisher Distributor or Service Organization every 6 years. Some of these units are in use in residential settings. The affected extinguishers have a steel cylinder with a welded neck ring and are between 19 to 21 inches tall, as depicted in the image below. This Alert does not apply to Kidde's smaller 2 1/2 and 5 lb. residential fire extinguishers.

Affected Products

Kidde 10 lb. industrial dry chemical fire extinguishers with black plastic Zytel® nylon valves in steel cylinders manufactured between 1991 and 2000

Additional Source Details

FieldValue
U R Lhttps://www.cpsc.gov/Recalls/2005/CPSC-Kidde-Announce-Recall-of-Industrial-Fire-Extinguishers
TitleCPSC, Kidde Announce Recall of Industrial Fire Extinguishers
Images › 1 › U R Lhttps://www.cpsc.gov/~/link/56fe2be7b5a74eccbb61b03e2e5914d4.jpg
Images › 1 › CaptionAffected model - Remove from service
Images › 2 › U R Lhttps://www.cpsc.gov/~/link/77e7dbb622bb4e04bcfc5f623f18d195.jpg
Images › 2 › CaptionNon-affected model - Leave in service
Images › 3 › U R Lhttps://www.cpsc.gov/~/link/a2c34d804dad43fb82e91ae0137463db.jpg
Images › 3 › CaptionExtinguisher Height Comparison
Hazards › NameThe nylon valves on these extinguishers can separate from the steel cylinder during the 6-year recharge service or shortly afterwards, creating a safety hazard to fire extinguisher service personnel and consumers.
Injuries › NameKidde has received five reports of valve separation during either technical service of the units or shortly afterwards, resulting in three reports of injuries.
Products › NameKidde 10 lb. industrial dry chemical fire extinguishers with black plastic Zytel® nylon valves in steel cylinders manufactured between 1991 and 2000
Products › TypeFire Extinguishers
Products › Category I D1939
Products › Number Of UnitsAbout 470,000
Recall I D3115
Remedies › NameFire Extinguisher Distributors and Service Organizations must immediately stop servicing all units covered under this Alert. Kidde has instituted a Fire Extinguisher Replacement Program ("Replacement Program") for all units covered by this Alert. If you are a Fire Extinguisher Distributor or Service Organization and you have not already received a copy of the Replacement Program, as outlined in Service Bulletin 007, please contact Kidde. Only professional Fire Extinguisher Distributors and Service Organizations should remove the affected units and the steps as outlined in the Replacement Program must be followed.
Retailers › NameCommercial fire equipment distributors and stores nationwide, between 1991 and 2000.
Recall Date2005-07-26T00:00:00
DescriptionThis Alert involves all Kidde 10 lb. dry chemical fire extinguishers manufactured with a black plastic Zytel® nylon valve assembly and a steel cylinder, between 1991 and 2000. These units were the subject of Kidde Service Bulletin 007 issued on July 21, 2004. These units were designed for commercial and industrial applications, and the majority of these units were placed into service in factories, plants, businesses and other commercial locations, as they require service by a qualified Fire Extinguisher Distributor or Service Organization every 6 years. Some of these units are in use in residential settings. The affected extinguishers have a steel cylinder with a welded neck ring and are between 19 to 21 inches tall, as depicted in the image below. This Alert does not apply to Kidde's smaller 2 1/2 and 5 lb. residential fire extinguishers.
Recall Number05589
Manufacturers › NameWalter Kidde Portable Equipment Inc., of Mebane, N.C.
Consumer ContactFire Extinguisher Distributors and Service Organizations should contact Kidde at 1-877-777-8170 between 8 AM and 5 PM ET Monday through Friday to participate in Kidde's Replacement Program. Only professional Fire Extinguisher Distributors and Service Organizations should call this number. Consumers who suspect that they may possess one of the industrial units covered by this Alert should not remove the unit and should contact Kidde at (800) 631-7377 between 8 AM and 5 PM ET Monday through Friday. Units should not be returned to the place of purchase. More information can also be obtained by visiting Kidde's Web site at www.kiddeus.com and referencing Kidde Service Bulletin 007 and Recall Alert.
Last Publish Date2024-12-20T00:00:00
Manufacturer Countries › CountryUnited States

Overview

  • Recalling FirmWalter Kidde Portable Equipment Inc., of Mebane, N.C.
Official Agency Alert