Home/Recalls/CPSC-04507
CPSCGeneral Alert

CPSC, Fire Control Instruments Announce Recall for Audio Evacuation Units

Published: October 30, 2003Recall ID: 04507Category: generalCountry: US

Reason for Recall / Hazard

The AEU can enter a "sleep" mode, where it does not communicate with the system. When this occurs, audible evacuation signals associated with the failed AEU will not operate and building occupants may not be warned of an emergency.

Product Description & Identification

All FCI AEUs (part number 1100-1171) manufactured prior to April 12, 2003. These AEUs are used in FireVac 7200 System Control Units. A label in the left center of the circuit board reads "FCI 7200" and "AEU." All V5 versions below V5.2-008 and V6 versions below V6.0.14 are included in the recall.

Affected Products

Audio Evacuation Unit

Additional Source Details

FieldValue
U R Lhttps://www.cpsc.gov/Recalls/2004/CPSC-Fire-Control-Instruments-Announce-Recall-for-Audio-Evacuation-Units-
TitleCPSC, Fire Control Instruments Announce Recall for Audio Evacuation Units
Images › U R Lhttps://www.cpsc.gov/s3fs-public/audio-evac-unit.jpg
Images › CaptionRecalled Audio Evacuation Unit
Hazards › NameThe AEU can enter a "sleep" mode, where it does not communicate with the system. When this occurs, audible evacuation signals associated with the failed AEU will not operate and building occupants may not be warned of an emergency.
Injuries › NameFCI has received seven reports of AEUs unexpectedly entering a "sleep" mode. No injuries have been reported.
Products › NameAudio Evacuation Unit
Products › TypeFire Warning Systems
Products › Category I D1941
Products › Number Of Units276
Recall I D2706
Remedies › NameFCI will provide a new software chip set for each FireVac System, at no charge.
Retailers › NameTo FCI distributors nationwide, from January 1998 through April 11, 2003, for a list price of $825.
Recall Date2003-10-30T00:00:00
DescriptionAll FCI AEUs (part number 1100-1171) manufactured prior to April 12, 2003. These AEUs are used in FireVac 7200 System Control Units. A label in the left center of the circuit board reads "FCI 7200" and "AEU." All V5 versions below V5.2-008 and V6 versions below V6.0.14 are included in the recall.
Recall Number04507
Manufacturers › NameFire Control Instruments, of Westwood, Mass.
Consumer ContactDistributors who do not receive the new software chip set or who have additional questions should contact their customer service representative at (800) 633-1311 between 8 a.m. and 5 p.m. ET, Monday through Friday.
Last Publish Date2025-03-24T00:00:00
Manufacturer Countries › CountryUnited States

Overview

  • Recalling FirmFire Control Instruments, of Westwood, Mass.
Official Agency Alert